O'Brien Boiler Services

Southern Cross Boiler

phoca_thumb_m_24th april 09-9aphoca_thumb_m_24th april 09-4aphoca_thumb_m_24th april 09-6aThe Southern Cross boiler by O’Brien Boilers is noted for its efficiency, economy of operation, rapid steaming ability and compact design.

It is designed and manufactured to AS1228 and meets the requirements of AS2593 Table 1.1 for unattended operation. Southern Cross features three pass flue gas circulation, tubeless construction, fully suspended combustion chamber, vertical disposition, and the absence of refractory.

Key features

  • Vertical, tubeless, 3 pass system
  • No refractory: wet back principle, low maintenance
  • High thermal efficiency, complete with stainless steel economiser
  • Quick steaming, ability to meet fluctuating demands
  • Full water space above, below, and around furnace chamber.
  • Water level probes within boiler drum
  • Replaceable diffuser feed pipe system
  • Anti-priming steam extraction apparatus
  • With accessible cleaning ports
  • Comes with an Economiser for added efficiency
  • Standard electrical connection to suit AS3000
  • Hold down lugs for safe transport
  • Compact design, polished steel appearance
  • All boilers hydrostatically tested and inspected
  • Provision for handling by either crane or forklift
  • Automatic blowdown Rated to 1000kpa

Three Pass System

As illustrated, high temperature flue gases travel upward in the first pass, allowing the walls of the cylindrical surface of furnace to absorb heat from the radiant flame and transfer it to the surrounding water wall. In the second pass, hot flue gases travel downward through a number of narrow passages formed by the fins attached to the external wall of the boiler drum. In the third pass the gases again travel upward through similar narrow passages prior to being exhausted through the chimney. Having three passes ensures maximum heat yield (in excess of 80%) and minimal loss. An additional (optional) economizer is mounted at the exhaust after the flue opening allowing maximum 3% increase in boiler efficiency. Additional feature is the cleaning port for exhaust allowing for oil fuel operation.

Model SC 100 SC 200 SC 300 SC 400 SC 500
Output Capacity (kW) 100 200 300 400 500
Evaporation F&A 100C kg/hr 160 320 480 640 800
Input mj/hr 450 900 1350 1800 2250
Heating Surface m2 3.7 7.41 11.11 14.81 18.51
Full Height "A" mm 1600 2000 2200 2600 2600
Case Height "B" mm 1450 1850 2050 2200 2200
Case Width "C" mm 1200 1250 1550 1678 1758
Overall Width "D" mm w/burner 1650 1750 1750 1850 1950
Skid Width "E" 900 900 900 1089 1089
Burner Height "F" 768 868 1068 1168 1168
Main Stream Value "G" 20 25 32 40 50
Feed Water Inlet 20 25 25 25 25
Safety Value 20 20 20 25 25
Blowdown Valve "H" 20 25 25 40 40
Flue "I" 175 250 250 300 300

scboilerthree_pass_system